Potential Transformer - Construction - Working - Theory - Phasor Diagram - Errors - Characteristics


Potential Transformer

Potential transformers are a type of instrument transformer and these transformers are used to measure the voltages of high transmission lines or any electrical circuits. Potential transformers are used to step down the high voltages. Their primary coils are connected to high voltage side and their secondary coils are connected to various instruments such as voltmeters, wattmeters, power factor meters etc. These potential transformers provide 100v to 150 v on their secondary winding so that the measuring instruments are connected easily according to their input voltages and these are sufficient to operate in this range of voltage. Measuring instruments such as wattmeters, voltmeters which are connected to the secondary winding of potential transformer provide low readings according to their input voltage. The exact readings are obtained from these measuring instruments by dividing the transformation ratio. So that we can easily obtain the exact amount of voltage with the help of potential transformer. Figure shows the potential transformer is connected with the voltmeter and how it is used when connected to the high voltage side below:





The potential transformers and the power transformers are same to each other only the difference between these is that potential transformers have special requirements for the measurement of various electrical parameters. These requirements are as follows:

  • Attenuation ratio must be accurately maintained in a potential transformer for measurement of electrical parameters.

  • Voltage drops should be reduced as possible and these are reduced by using proper design of core and by using large conductors.

  • The load voltage / secondary voltage should be minimum and of few volt-amperes so that the measuring instruments are connected easily on the secondary of potential transformers.


Construction

A potential transformer consists of its so many parts in its construction and these parts of potential transformer (PT) are discussed below:

Core

Potential transformers are made with its two types of core construction and these two types are core type PT and shell type PT. The core type PT’s are used for low voltage while the shell type PT’s are used for high voltage. The core laminations of both shell type and core type PT’s are assembled with so many care to avoid from air gap between the joints.

Winding

The both windings (primary and secondary) are coaxial cable type so that the leakage reactance is minimized. The secondary winding is placed nearer to the core and the primary winding is twisted on the secondary winding. The primary winding is made of a single coil when PT is required for low voltage use otherwise the primary winding is of double coil for high voltage uses.

Insulation

The insulation is required to separate the primary and secondary winding so cotton tape and varnish are most widely used as an insulation in PT’s. PT’s are filled with solid compounds for low voltage otherwise the insulation is oil immersed.

Bushings

The bushings of PT are consisting of various types some are oil filed and these bushings are used for oil filled potential transformers. Some PT’s have two bushings for high voltage and some has only one bushing for high voltage and some have two bushings and these are grounded and these not require any neutral connections.



Working

Potential transformers are commonly used for the measurement of voltage and power of a distribution lines or transmission lines and it is used for the measurement of high voltage and power between the high power cable and mainly used in grid stations, power stations and on those places where power is generated and controlled for transmission and distribution for power. The working of a potential transformer is that it steps down the high voltage and provide the power according to the reading of a measuring instrument which is installed for the measurement of voltage or power. So, its main purpose is to provide voltage according to the measuring instrument so that the power is controlled according to its rating.

Theory of Potential Transformer

Figure shows the equivalent circuit of potential transformer and the theory of potential transformer is as under:



Vp = primary voltage
Ep = induced voltage in primary winding
Vs = secondary voltage
Es = induced voltage in secondary winding
Ip = primary current
Is = secondary current
I0 = no load current
Ic = core loss component of current
Im = magnetizing component of current
Rp = resistance of primary winding
Xp = reactance of primary winding
Rs = secondary winding resistance
Xs = secondary winding reactance
Rc = imaginary resistance / core loss
Xm = magnetizing reactance
Re = resistance of external load
Xe = reactance of external load
Np = primary winding turns
Ns = secondary winding turns
N = turn ratio
Φ = flux of potential transformer
δ =       Phase angle between secondary winding voltage and secondary winding 
β =      Phase angle between primary current and Secondary current
α =      Phase angle between no-load current I0 and flux φ



The flux is conspired along the x axis. Im is in phase with flux. Ic leads by Im 900. The sum of Ic and Im produces no load current Io. Ep is in the phase with the core loss component of current Ic. Es is 180o out of phase with the primary winding voltage Ep. Secondary voltage Vs are obtained by subtracting the IsRs and IsXs from secondary voltage.

Phasor Diagram of Potential Transformer (PT)

The phasor diagram is displayed below:


The phase angle between the primary voltage and the secondary voltage is called the phase angle of PT. This phase angle is ideally equal to zero because these two phasors are in same phase.
From the phasor diagram we have, 


But in reality, the phase angle is very small and the primary and secondary voltage are perpendicular to the flux and then;
Eq pt 2

Where Rs is equivalent resistance of PT and Xs equivalent reactance of PT.

Phase Angle of Potential Transformer (PT)
From the phasor diagram the terms Ip and Is are less compared to large voltage and these terms are neglected thus we get:




Errors in Potential Transformers (PT)

There are two types of errors occurred in potential transformers. These errors also launch in measurement of voltage. These errors are occurred in terms of magnitude of the measured values. These errors are discussed below:

Ratio Errors

The ratio of the potential transformer is the difference between the minor and actual transformation ratio. This error is occurred in measurements of voltage and these errors are occurred due to the less ratio between the transformation ratio.

Phase Angle Errors

Phase angle errors are occurred during the measurements of power. In these errors, the primary circuit of the potential transformer cannot be attained by multiplying the voltage which are measured with voltmeter. These errors are determined by the resistance and reactance and on the no-load current of the transformer.

Reducing Errors in Potential Transformer (PT)

The following points are used for the reduction of errors in potential transformer:
To reduce the length of magnetic path in the core. With this, the no load primary current is reduced.

By using thick conductors and to reduce the length of mean turn of the windings.

By keeping close primary and secondary windings to each other. This reduces the leakage flux and the leakage reactance.

By reducing the length of wound winding over the core. This will reduce resistance of winding and provide high flux densities in the core.

Characteristics of ON Load Potential Transformer (PT)

Characteristics of potential transformer are determined through the phasor diagram which is shown above and determination between the ratio errors and phase angle errors of potential transformers. The following are the effects of various electrical parameters through which we will know the characteristics of practical potential transformer.

Effects of Changing in Secondary Voltage of Potential Transformer

When we increase the secondary voltage of the potential transformer then the secondary current also increases and this secondary current also increases the primary current of the potential transformer. Thus the voltage drops are produced in both primary and secondary winding and increases with respect to increase in primary and secondary currents. The secondary voltage are reduced according to the primary supply voltage. So, this effect increases the transformation ratio (Vp/Vs where Vp are the primary voltage and Vs are the secondary voltage) and it also increases the ratio error and phase angle error and these errors remain linear in position as shown in the figure below:





Effects of Changing in Power Factor of Secondary Voltage

According to the phasor diagram of potential transformer, the secondary current lags in arrears to the secondary voltage and the phase angle difference remains positive. When we lower the power factor, this phase angle increases and it moves absent from secondary voltage. The phasor diagram represents that the primary current closes to no load current and primary and secondary voltage are in phase with induced voltage in primary and secondary voltage. The primary voltage remains same and the transformation ratio increases due to reduction in power factor. The figure below identifies the phase angle and ratio errors in potential transformer according to changes in power factor of secondary voltage.